AC Speed Controller Troubleshooting

AC Tech Speed Controller Faults.

SCL = 220V = Purple

SCM = 110V = Red

Fault codes

-- = not a fault code, controller in stand by

LF = Line fault, low AC power, have customer turn power on and off

UF = Start Fault, check toggle switch

CF = corrupted EPM chip

F1 = Missing EPM chip

CP = control pad, use up and down arrows to run watermaker, check programming.

  1. Enter PROGRAM MODE by pushing the Mode button. This will activate the passwordprompt.
  2. Enter the password with the up and down buttons. When the display reads 25, press Mode. The display will read P01 to indicate that you have entered program mode.
  3. Using the up and down buttons select the desired Parameter (e.g.P31 for setting run speed.) Press Mode to display the current setting. The speed settings are displayed in Hertz (cycles per second AC output power frequency.)
  4. Use the up and down buttons to change the setting.

Default password =225

Spectra password = 25 (changed in P44)

Parameter

700 MPC 5K

1000 MPC 5K

700 C

1000c

3,4,5,10,11,

12,19,24,27,

32,42

All defaults

All defaults

All defaults

All defaults

P31

38/run

51/run

38/run man

51/run man

P33

28/low

38/low

15/service, flush, purge

15/service, flush, purge

P35

35/service

35/service

38/Run hi

51Run hi

P36

15/flush

15/flush

28/Run low

38/Run low

P44

25/password

25/password

25/password

25/password